PRODUCTS
FC-RLD-HP Heavy-duty Plus Bubble-tight(Zero leakage) Air Tight Dampers
FC-RLD-HP Bubble-tight Air Tight Dampers are designed to provide high level tightness at extremely high pressure, up to 100KPa differential pressure and can stand pressure difference up to 180KPa without permanent deformation which may affect its tightness performance. Therefore, this product is capable to tackle the most critical situations for key buildings or systems such as NBC filtering system of hardened shelters, control room of nuclear power plant and control buildings of OGP industry.
Additional information
Provide bubble-tight tightness at differential pressure up to 100KPa | Offers outstanding protection even there is significant air pressure change on damper. |
---|---|
Stand high pressure in elastic range | Able to stand 180KPa without deformation. |
Maintain all functions after high pressure | Offer the reliable protection under critical situations such as dramatically fluctuating air pressure. |
Good corrosion resistant performance | Frames are made of chemical-resistant materials such as galvanized steel, nickel coated steel, stainless steel, etc. |
Frame material | Galvanized steel/Nickel coated steel/SS304/SS316 |
Blade material | Galvanized steel/Nickel coated steel/SS304/SS316 |
Working pressure | 180KPa |
Zero-leakage pressure | 100KPa |
Sealing type | Fluoro rubber |
Leakage rating Standards (EN1751:2014 Ventilation for buildings. Air terminal devices. Aerodynamic test.) | FIGURE 1 (Blade): Class 4 FIGURE 2 (Casing): <0,25 dm3/h |
Leakage rating Standards (AMCA 500D-18 Laboratory Methods of Testing Dampers for Rating) | FIGURE 5.8 Bubble-tight (Zero Leakage) at 100KPa |
Leakage rating Standards (KTA 3601-2017 Ventilation Systems in Nuclear Power Plants) | Class 1 |
Certificates | Product is certified by ERUOFINS EXPERT SERVICES, Finland. Test report available upon request. |
Application | NBC shelters, OGP, Chemical, Nuclear power, Others |